Fire stopping vs compartmentation: what's the difference?

Last reviewed:

Reviewed by Tom Linstead, Founder and Partner, RiSKFiX LLP

Compartmentation is the division of a building into fire compartments using fire-resisting walls and floors. Fire stopping is the sealing of gaps where services and joints pass through that construction. Compartmentation is the barrier; fire stopping keeps the barrier intact.

What does compartmentation do?

It limits the spread of fire and smoke, protects escape routes and gives people time. Where compartments should be is set out in a building's fire strategy, often with compartmentation plans.

What does fire stopping do?

Each penetration through a compartment wall or floor is a weak point. Fire stopping restores the fire resistance of the wall or floor at that point. Penetration seals are tested to BS EN 1366-3:2021 and classified to BS EN 13501-2:2023.

Which survey do you need?

A fire stopping survey focuses on the seals. A compartmentation survey checks that the walls, floors and cavity barriers themselves are continuous, as well as the fire stopping within them. Many clients combine the two.

Frequently asked questions

Can a building have good fire stopping but poor compartmentation?

Yes. Seals may be sound while a compartment wall stops short at ceiling level, leaving a route for fire and smoke above the ceiling.

Where do compartmentation plans come from?

They are produced as part of a fire strategy, normally by a qualified fire engineer.

Which guidance covers compartmentation?

Approved Document B (2019 edition incorporating 2026 amendments), BS 9999:2017 and BS 9991:2024, depending on the building and its fire strategy.